Product characteristics
|
Number of inputs and outputs |
Number of digital outputs: 1; Number of analog outputs: 1 |
Measuring range |
0...999.5 °C |
32...1831 °F |
|
Application
|
Application |
asphalt; coated metal; liquids; glass; rubber; wood; ceramics; plastics; lacquers; food products; paper; fabric |
Electrical data
|
Operating voltage [V] |
18...32 DC; (to SELV/PELV) |
Current consumption [mA] |
< 50 |
Min. insulation resistance [MΩ] |
100; (50 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
< 1 |
Inputs / outputs
|
Number of inputs and outputs |
Number of digital outputs: 1; Number of analog outputs: 1 |
Inputs
|
Test input |
type 3 (IEC 61131-2) |
Outputs
|
Total number of outputs |
2 |
Output signal |
switching signal; analog signal; IO-Link; (configurable) |
Electrical design |
PNP |
Number of digital outputs |
1 |
Output function |
normally open / closed; (configurable) |
Max. voltage drop switching output DC [V] |
2.5 |
Permanent current rating of switching output DC [mA] |
150 |
Number of analog outputs |
1 |
Analog current output [mA] |
4...20 |
Max. load [Ω] |
500 |
Short-circuit protection |
yes |
Type of short-circuit protection |
yes (non-latching) |
Short-circuit proof |
yes |
Overload protection |
yes |
Monitoring range
|
Wave length range [µm] |
8...14 |
Measuring/setting range
|
Measuring range |
0...999.5 °C |
32...1831 °F |
|
Set point SP |
1...999.5 °C |
34...1831 °F |
|
Reset point rP |
0...998.5 °C |
32...1829 °F |
|
Analog start point |
0...949.5 °C |
32...1741.1 °F |
|
Analog end point |
50...999.5 °C |
122...1831 °F |
|
In steps of |
|
Resolution
|
Resolution of switching output [K] |
0.5 |
Resolution of analog output [K] |
0.2; (+ 0.03 % of the set measuring span) |
Resolution of display [K] |
0.5 |
Accuracy / deviations
|
Accuracy [K] |
< ± 1 %; (of measured value, min. 2 K (degree of emission = 1, T = 23 °C)) |
Repeatability [K] |
1 |
Reaction times
|
Response time [ms] |
100
|
Software / programming
|
Adjustment of the switch point |
Programming buttons |
Parameter setting options |
Analog range; normally open / closed; switch-on/switch-off delay; Damping; Peakhold; emissivity; simulation function |
Interfaces
|
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
SIO mode |
yes |
Required master port class |
A |
Process data analog |
16 |
Process data binary |
1 |
Min. process cycle time [ms] |
3.6 |
Supported DeviceIDs |
Type of operation |
DeviceID |
default |
716 |
|
Operating conditions
|
Ambient temperature [°C] |
0...65 |
Storage temperature [°C] |
-20...80 |
Max. relative air humidity [%] |
95; (non condensing) |
Protection |
IP 65 |
Tests / approvals
|
EMC |
DIN EN 61000-6-2 |
|
DIN EN 61000-6-4 |
|
|
Shock resistance |
DIN EN 60068-2-27 |
30 g (11 ms) |
|
Vibration resistance |
DIN EN 60068-2-6 |
5 g (10...2000 Hz) |
|
MTTF [years] |
88
|
Mechanical data
|
Weight [g] |
411.5 |
Housing |
Threaded type |
Dimensions [mm] |
M30 x 1.5 |
Thread designation |
M30 x 1.5 |
Material |
threaded sleeve: stainless steel (1.4305 / 303); polyester |
Lens material |
Infrared transparent crystal lens with anti-reflex coating |
|
Displays / operating elements
|
Display |
Display unit |
2 x LED, yellow |
Switching status |
1 x LED, yellow |
Function display |
7-segment LED display, 4-digit |
Measured values |
7-segment LED display, 4-digit |
|
Operating elements |
|
Accessories
|
Items supplied |
|
Remarks
|
Remarks |
Use a screened cable to protect infrared temperature sensors from interference. |
The screen must be connected to the housing of the sensor via the connector. |
|
Pack quantity |
1 pcs. |
Electrical connection
|
Connection |
Connector: 1 x M12 |
Diagrams and graphs
|
|
1 |
diameter of the measured spot |
2 |
measuring distance |
|